2.3 Bolt-In Installation

2.3.1 Preparation of Boat Structure

The Seakeeper Drawing No. 90590, Seakeeper 2 Generic Installation Guide shows various structural arrangements to support the installation of the Seakeeper. The Generic Installation Guide offers above and below deck installation arrangements with fiber-reinforced plastic (FRP) and aluminum structures, which should provide solutions for most vessels. The Seakeeper 2 is affixed to the hull structure via four bolts in the
Seakeeper 2 frame. Depending on the structure to which the Seakeeper is fastened, blind threaded holes or through-bolting can be utilized.

Refer to Seakeeper Drawing No. 90487, Seakeeper 2 Bolt in Installation Details. Important dimensional and load information is given in this drawing that will impact the design details of the structure that will receive the Seakeeper. It is assumed that a proper structural analysis has been performed for the hull structure to which the Seakeeper will be fastened to ensure proper strength margins for the loads the Seakeeper will create during operation.

The hull structure supporting the Seakeeper should be installed so the Seakeeper is parallel to the waterline in the transverse direction and within 1 degree longitudinally.

In addition, the four areas on top of the structure on which the Seakeeper 2 frame and isolation gaskets will rest, need to be co-planar within .06 in. (1.5 mm) to minimize potential distortion of Seakeeper support frame when installed. The isolation gaskets are only used when the Seakeeper 2 is mounted to a dissimilar metal structure.

Seakeeper offers an optional installation template kit, P/N 90473, which contains four plates that mimic the mating surfaces of the four feet located on the Seakeeper ’s foundation. These plates have 4 holes located at the same centers as the mounting holes on the Seakeeper 3.The fixture locates the hole patterns at the proper spacing both in the forward-aft direction and the port-starboard direction. See Figure 4 below. Once assembled, the fixture can be used to check clearances and alignment of the hull structure.

Note: Do NOT use the installation fixture to establish the Seakeeper envelope dimensions. Refer to Drawing No. 90487 – Seakeeper 2 Bolt-In Installation Details, for envelope dimensions. A 3-D model of the Seakeeper is available on the Seakeeper Dealer Access website (www.seakeeper.com) to aid in designing the Seakeeper foundation and the space around the Seakeeper

NOTE: MAKE SURE NO OBSTRUCTIONS FROM THE HULL STRUCTURE CAN BE SEEN WITHINTHE INSIDE OF THE INSTALLATION TEMPLATE KIT (INSIDE THE MARKED RED LINES) AS SEEN IN FIGURE 5. REFERENCE SEAKEEPER DRAWING NO. 90487 – SEAKEEPER 2 BOLT-ININSTALLATION DETAILS

Figure 4 – Exploded View of Installation Fixture
Figure 5 – Seakeeper 2 Longitudinal Bolt-In Clearance Dimensions

CAUTION: Tight clearances from cable guide bands to hull structure. See above Figure 5 for dimensions and reference Seakeeper Drawing No. 90487 – Seakeeper 2 Bolt-In Installation Details, for complete Seakeeper 2 envelope.

2.3.2 Transfer of Holes to Boat Structure

  1. Lower assembled fixture onto hull structure.
  2. The four areas where the feet of the Seakeeper will rest should be coplanar to within .06 in. (1.5 mm). See Figure 6.
  3. Align fixture in desired location and transfer holes from fixture plate to the hull structure using provided transfer punch. Note that holes in fixture plate are ø0.60 in. (15.138 mm).
  4. Remove fixture and drill and tap M14X2.0 Helicoil threaded insert holes in hull structure at marked locations to mate with holes in the Seakeeper foundation. Take special care to drill perpendicular to mounting surface. A drill guide is recommended. Remove any impeding obstructions.
Figure 6 – Longitudinal Bolt-In Hole Transfer Fixture

2.3.3 Installation of Seakeeper

  1. Lower Seakeeper into position onto the hull foundation beams and align over drilled holes. Apply a small bead of marine sealant (e.g., SILI-THANE 803 or equivalent)between mating surfaces of Seakeeper frame and hull structure to prevent moisture wicking into bolt holes.
    1. For dissimilar metal foundations locate and position 4 isolation gaskets onto foundation beams and apply a small bead of marine sealant (e.g., SILI-THANE 803or equivalent) between both mating surfaces of each isolation gasket where it contacts the beam and the Seakeeper (See Figure 7).
Figure 7 – Seakeeper 2 Longitudinal Bolt-In Installation
  1. Install mounting bolts:
    1. For Blind Hole Installations, install the Seakeeper supplied Grade 10.9, M14-2.0 x90 mm fasteners or alternative Grade 10.9, M14-2.0 bolts to maintain a minimum thread engagement of 0.83 in (21 mm). If Seakeeper supplied bolts do not achieve the minimum thread engagement because of the lamination thickness or structure, longer bolts of the same specification (M14-2.0, Grade10.9) should be sourced. If tapping directly into a metal frame shorter bolts maybe required. Apply a moderate coat of marine anti-seize (e.g., SAF-T-EZE nickel grade anti-seize, SBT-4N or equivalent) to the threads of each bolt and include a small bead of marine grade sealant (e.g., SILI-THANE 803 or equivalent) under each bolt head and washer before installation. See Figure 8 below.
    2. For Through-Bolt installation install the Seakeeper optional Thru-Bolt Kit (P/N 90636) Grade 10.9, M14-2.0 x 100 mm fasteners with a minimum of 2 threads passing through the nut If Seakeeper supplied bolts do not pass entirely through the Extra Wide / Heavy Hex Nut because of the frame thickness, longer bolts of the same specification (M14-2.0, Grade 10.9) should be sourced. Apply a moderate coat of marine anti-seize (e.g., SAF-T-EZE nickel grade anti-seize, SBT-4Nor equivalent) to the threads of each bolt and include a small bead of marine grade sealant (e.g., SILI-THANE 803 or equivalent) under each bolt head and washer before installation. See Figure 9 below.
Figure 8 – Seakeeper 2 Blind Hole Bolt Stack Arrangement
Figure 9Seakeeper 2 Thru-Hole Bolt Stack Arrangement

3.0 Electrical Installation

3.1 Electrical Installation Introduction

This section for electrical installation explains how to mount the electrical equipment and how to connect the electrical cables.

Reference Documents & Drawings:

Seakeeper 2, Front Oblique View
Seakeeper 2, Rear Oblique View
High Current 12VDC Power Input, 2AWG

This image has an empty alt attribute; its file name is Cable-7-2x16AWG-Pump-Pwr-Input.jpg
Low Current 12VDC Power Input Cable,
P/N 20248
SW Pump 12 VDC Power
Input Cable, P/N 30327
This image has an empty alt attribute; its file name is Cable-5-2x16AWG-Pump-Pwr-Output.jpg
SW Pump 12 VDC Power Output Cable, P/N 20334

M12 D-Code, Male-Female Cable, 32.8 ft (10 m), P/N 30330
NMEA 2000 Drop Cable,
19.7 ft (6 m), P/N 30332

Figure 10 – Electrical Equipment for Seakeeper 2

3.2 Electrical Equipment Power Connections

3.2.1 High Current 12 V Power Input

Figure 11 – Seakeeper 2 DC Power Input & Output Connections

High Current 12 VDC Power Source Requirements

SourceBattery Bank, 12 VDC, Marine, Deep Cycle (AGM battered recommended)
Voltage Range10 – 15 VDC
Continuous Current75 A
Overcurrent Protection100 A (Customer Supplied)

High Current 12 VDC Power Connection Instructions

  1. High Current 2 AWG conductors connect the Seakeeper to the DC source are supplied as length 13ft (4 m). Approximately 3 ft (1 m) is routed inside the Seakeeper frame.
  2. Conductor length may be increased, but changing from 2 AWG to larger wire size does not allow longer length than 30 ft (9 m) each. The length limit is required to limit the inductance from the high current conductors.
  3. Use the shortest length and most direct route to the battery bank as possible.
  4. Bind positive (B+, red) & negative (B-, black) conductors together throughout entire length and do not coil.
  5. Connect positive conductor (B+, red) through dedicated over-current protection device (customer supplied) and a dedicated isolation switch (customer supplied) then directly to battery positive terminal.
  6. Connect negative conductor (B-, black) directly to battery negative terminal.
This image has an empty alt attribute; its file name is SEAKEEPER-2-2AWG-Conductor-Connections-At-Circuit-Breaker-and-Battery.jpg
Figure 12 – 2 AWG Conductor Connections at Circuit Breaker and Battery
  1. If the 2 AWG high current 12 V power input conductors are shortened or lengthened, use heavy-duty eyelet (closed end) terminal such as Molex 19221-0235 and follow instructions on Seakeeper Drawing No. 90470 – Seakeeper 2 Cable Block Diagram, sheet 2.
  2. The bare wire strands should extend fully into the barrel of the heavy-duty eyelet and be crimped in two places if possible then sealed with double-wall heat shrink tubing. Crimp heavy-duty terminals with Quick Cable 4245 Crimp Tool, Molex 19284-0034 Crimp Tool, or equivalent using manufacturer’s instructions.
Figure 13 – High Current Conductor Crimping Instructions

3.2.2 Low Current 12 V Power Input

Low Current 12 VDC Power Source Requirements

SourceBattery Bank, 12 VDC, Marine, Deep Cycle
Alternate SourcePower Supply / Battery Charger, 12 VDC
Voltage Range11 – 15 VDC
Continuous Current9 A
Overcurrent Protection15 A (Customer Supplied)

Low Current 12 VDC Power Connection Instructions



Reversing polarity on the DC power input to the Seakeeper can result in damaging the electronics in the control system.

  1. Install Seakeeper-provided Low Current DC Power Input Cable, (P/N 20248) to battery bank.
  2. Connect control power positive conductor (B+, red) through dedicated over-current protection device (customer supplied) and a dedicated Seakeeper isolation switch (customer supplied). A 2AWG, B+ conductor (red), is capable of carrying the current for both the High Current, Low Current, and Seawater Pump from the 12VDC power supply to the dedicated battery isolation switch.
  3. Connect negative conductor (B-, black) directly to battery minus terminal or negative DC bus bar.
  4. Before connecting Low Current Power Cable to Seakeeper, check for proper voltage and polarity with a DC multimeter using Figure 14 below.

When energizing DC power the first time, if display does not power up immediately then disconnect and inspect connector polarity.

Figure 14 – Low Current 12 VDC Power Input Connector Contact Assignments (Front)
  1. Connect low-current control power cable to Low Current 12 VDC power input connector on the Seakeeper, Deutsch DTP04-2P connector.

3.2.3 DC Seawater Pump 12 V Power Output

DC Seawater Pump 12 VDC Power Source Specifications

Source12 VDC from the Seakeeper
Voltage Range10 – 15 VDC
Continuous CurrentOn-demand, typically ~10 A
Overcurrent ProtectionPer pump specification, max 15 A

DC Seawater Pump 12 VDC Power Input Connection Instructions

  1. Located the Seawater Pump Power Input Cable (P/N 30327) for Seakeeper 2 “SW Pump DC In” connection on Seakeeper 2 wire harness (as shown in Drawing No. 90470).
  2. Connect the 16 AWG positive conductor (red) through dedicated overcurrent protection device (customer-supplied), maximum of 15A, to dedicated battery isolation switch.
    • The High Current, 2AWG B+ conductor (red), is capable of carrying the current for both the High Current, Low Current, and Seawater Pump from the 12VDC power supply to the dedicated battery isolation switch.
  3. Connect the 16 AWG negative conductor (black) directly to battery negative terminal or DC main negative bus bar.
  4. Before connecting the SW Pump Power Input Cable to the Seakeeper 2, check for proper voltage and polarity with a DC multimeter using Figure 15 below.
  5. Connect SW Pump Power Input Cable to Seawater Pump 12 VDC In connector on the Seakeeper, DEUTSCH DT04-2P connector.
Figure 15 – 12 VDC Seawater Pump Power Input Connector

Seawater Pump 12 VDC Power Output Connection Instructions

  1. Locate the Seawater Pump Power Output Cable (P/N 20334) for “SW Pump 12VDC Out” connection on Seakeeper 2 wire harness (as shown in Drawing No. 90470).
  2. Pumps rated at 12 VDC, 15 amps maximum, customer-supplied, must be configured with a Deutsch DT series, 2-pin receptacle to mate with the connector as shown in Figure 16.
    • TE Connectivity (Deutsch) DT04-2P Receptacle, 2-Way, for Male Pins (qty 1)
    • TE Connectivity (Deutsch) 0460-202-1631 Pin, Solid, Gold-plated, Size 16, 16-20 AWG (qty 2)
    • TE Connectivity (Deutsch) W2P Wedgelock for 2-Way DT Receptacle (qty 1)
Figure 16 – Seawater Pump DC Output Power Cable End
  1. The Seawater Pump Power Output Cable must be routed and installed in the vessel from the Seakeeper 2 “SW Pump 12VDC Out” Deutsch connector plug (pins end) to the DC seawater pump cable Deutsch connector (socket end).
  2. Connect Seawater Pump Power Output Cable (socket end) to the customer-supplied receptacle end (pins end). The recommended wiring arrangement is shown in Figure 17
  3. Seakeeper DC Seawater Pump Assembly (P/N 30331), which is prewired for the Seawater Pump Output Cable, is available as an option with the Seakeeper 2.
Figure 17 – Seawater Pump Power Output

3.3 Electrical Equipment Ground Connections

Seakeeper to Vessel Ground Connection Instructions

  1. Connect the Seakeeper foundation ground stud, shown in Figure 18, to vessel ground.
    1. Install Ground Wire (4 AWG or 25 mm2, Customer Supplied) from the M6 brass ground stud to vessel grounding bus to comply with:
      1. EM / IEC 60204-1 Clauses 6.3.3 and 8.2.3.
      2. ABYC E-11 July 2018 Clauses 11.5.2 and 11.16.1.

NOTE: ONLY USE THIS LOCATION FOR GROUNDING THE SEAKEEPER TO THE VESSEL GROUND.

Figure 18– Ground Stud on Frame

b. A proper ground connection is critically important for corrosion
protection and helps to ensure the ignition protection of the unit
by ensuring it does not carry any stray current.

c. NOTE: the ground is not referring specifically to a bonding system
but for outboard boats generally refers to the outboard engine
negative terminal, or its bus, to the DC grounding bus. This connection
shall be used only as a means of maintaining the negative side of the
circuit at ground potential and is not to carry current under normal
operating conditions. See Figure 19.

Figure 19 – ABYC E-11, figure 4A, Typical Outboard DC System

3.4 Display Connection

3.4.1 Seakeeper 2 Display Options

A Seakeeper display is required with the installation of a Seakeeper 2 to support the full functionality of the unit through the Seakeeper App in addition to the ConnectBox. The Seakeeper App provides an interface for controlling the Seakeeper 2 or viewing the Settings, Service, Info, and Alarm pages. The Seakeeper ConnectBox can be helm-mounted to provide an additional interface for the control of the Seakeeper 2 but does not replace the need for a Seakeeper compatible display.

The Seakeeper 2 has several options for establishing a Seakeeper display interface to support the Seakeeper App:

  1. Preferably, connect the Seakeeper 2 to a compatible Multifunction Display (MFD).
  2. Install an optional Seakeeper 5″ Touch Display.
  3. A combination of a compatible MFD and an optional 5″ Touch Display is also available, as seen in Figure 19 below (See drawing 90470).

Figure 20 provides a schematic of the display options. The subsequent sections outline the instructions and references for connecting the Seakeeper 2 to each of these display options.

Figure 20 – Serial Communications Link for Operator Station

3.4.2 Connecting to Compatible MFD

  1. The Seakeeper 2 can be connected to a variety of available MFD systems. Refer to the Technical Bulletins Section of the Seakeeper Technical Library for manufacturer specific MFD compatibility technical bulletins.
    1. MFD specific Technical Bulletins will be updated regularly as new MFD systems become compatible. Currently Garmin, Raymarine, NAVICO, and Furuno offer compatible MFD models.
    2. Once a compatible MFD has been selected, refer to the appropriate manufacturer specific Technical Bulletin for integration instructions.
  2. Connect Seakeeper-supplied Ethernet Adapter, M12 D-Code, 32.8 ft (10 m), cable to MFD manufacturer-specific Ethernet adapter cable (See Figure 21). Custom Ethernet cables for specific MFD manufacturers are available through Seakeeper and must be purchased with the Seakeeper 2 if connecting to an MFD.
Figure 21 – ConnectBox to MFD Connection

3.4.3 Connecting to an Optional Seakeeper 5″ Touch Display

If not utilizing a compatible MFD display, a Seakeeper 5” Touch Display must be purchased from Seakeeper. The Seakeeper 5” Touch Display (P/N 90467) includes the components shown in Figure 22 and will be integrated with the ConnectBox.

Figure 22 – Seakeeper 5″ Touch Display Components (P/N 90467)
  1. Determine location of Seakeeper 5” Touch Display:
    1. The desired location of the 5” Touch Display must be determined with respect to the vessel’s arrangement.
    2. The 5” Touch Display should be located on or near the helm or another easily accessible location.
  2. Route CAN communications cable:
    1. The CAN Cable Assembly is a 32.8 ft (10 m) shielded cable that connects the ConnectBox to the 5” Touch Display.
    2. The CAN cable assembly must be routed and installed in the vessel from the Seakeeper wire harness CAN Tee to the Tee Adapter at the Seakeeper 5” Touch Display, included with P/N 90467.
  3. Install Seakeeper 5” Touch Display equipment:
    1. Console space required: Approx. 5.24 W x 3.70 H in. (133 x 94 mm)
    2. Mounting Instructions, Surface Mount: see Envelope and Mounting Details, in Drawing No. 90438 – 5” Operator Display Envelope and Mounting Details.
  4. CAN communications tee adapter and terminator mounting instructions:
    1. Console space required, Rear: Approx. 4 W x 3 H in. (102 x 76 mm), rear
    2. Mounting Instructions: Rear mount on vessel console panel, within 2 ft (0.6 m) of Display.
    3. Hardware required: One mounting screw for .197 in. (5 mm) diameter mounting hole on Tee Adapter.
  5. Connect Seakeeper 5” Touch Display Equipment:
    1. The Seakeeper 5” Touch Display is connected in accordance with Drawing No. 90470 – Seakeeper 2 Cable Block Diagram, as shown in Figure 23.
Figure 23 Seakeeper 5″ Touch Display Connection

3.4.4 NMEA 2000 Network Connection

The Seakeeper 2 requires a connection to the vessel’s NMEA 2000 network backbone via a drop cable for access to the GPS signal. The Seakeeper 2 will monitor information on the NMEA network to support and optimize the performance of the Seakeeper 2. If no GPS signal is detected, a warning will appear on the Seakeeper display. The Seakeeper will not spool-down, but the operation of the unit will be limited until the GPS signal returns.

  1. Install customer-supplied NMEA 2000 Tee Adapter (space required: approximately 4 W X 3 H in. (102 X 76 mm).
  2. Connect NMEA Backbone to Tee Adapter. NOTE: NMEA drop cable can be no longer than 19.6 ft (6 m) in length.
  3. Connect Seakeeper-supplied NMEA cable (P/N: 30332) to the customer-supplied NMEA 2000 Tee Adapter on vessel’s NMEA 2000 backbone.
    1. An active NMEA 2000 compatible GPS signal is required on the vessel’s NMEA 2000 backbone to operate the Seakeeper 2.
      • If no GPS signal is detected, a Speed Over Ground (SOG signal) warning will be present on the Seakeeper app. See TB-90640 for NMEA connectivity guidance.

3.4.5 ConnectBox Helm Mounting – Optional

  1. Console space required: Approx. 3.41 L x 4.15 W in. (87 x 106 mm).
  2. Mounting Instructions, Surface Mount: See Drawing No. 90558 – ConnectBox Helm Mounting Kit, for details.
  3. Mount ConnectBox Replacement Blank insert into Seakeeper 2 enclosure at the original location of the ConnectBox.

4.0 Cooling Installation

4.1 Cooling Installation Introduction

Reference Documents & Drawings

The Seakeeper 2 is shipped with the cooling circuit filled and ready for use. The Seakeeper 2 requires connection to a raw water pump, referred to as the seawater pump, to cool the closed loop cooling circuit on the unit.  The required seawater flow through the Seakeeper 2 heat exchanger is between 2 – 6 GPM (7.6 – 22.7 LPM), under all vessel operating conditions. Prior to operation, confirmation of glycol level is required.

Seakeeper offers a compatible self-priming DC Seawater Pump (P/N 30331) that is prewired for the Seakeeper 2 Installation and covered under the standard Seakeeper warranty. See Drawing No. 30331, SeaFlo Seawater Pump Assembly for details and the Seakeeper Options and Accessories Price List for pricing information.

Figure 24 Seakeeper 2 Cooling system Components

4.2 Installation Considerations

  1. The installer is responsible for supplying a dedicated seawater pump and associated plumbing. An optional seawater pump can be purchased through Seakeeper, P/N 30331.
  2. Seawater connections on the Seakeeper heat exchanger mate with ¾ in. (19 mm) hose.
  3. The seawater pump is powered via the “SW Pump 12 VDC Out” connection on the Seakeeper 2 wire harness, as outlined in Electrical Installation Section.
  4. The seawater pump operates on 12 VDC with a max overcurrent protection rating of 15 A.
  5. A dedicated through-hull fitting should be installed for each Seakeeper unit onboard the vessel to ensure sufficient seawater flow to each unit.
  6. It is recommended that the seawater pump is located below the waterline, as close to the baseline of the vessel as practically possible, to maintain positive inlet pressure on the pump in all operating conditions.
  7. A self-priming seawater pump may be required to maintain water flow in all underway conditions. Cavitation can occur at the seawater inlet and potentially cause an air-lock condition restricting seawater flow to the heat exchanger.
  8. Maximum allowed seawater pressure in heat exchanger is 20 psi (1.4 bar)
  9. Seawater flow requirement through heat exchanger is 2 GPM (7.6 LPM) minimum and 6 GPM (22.7 LPM) maximum under all operating conditions of the boat. When sizing seawater pump, installer should factor in losses for raw water plumbing. In addition to initial operation at dock, new Seakeeper installations should be checked to be within the flow requirements while vessel is at speed. Flows higher than 6 GPM (22.7 LPM) could affect heat exchanger life.

4.3 Connecting Seawater to Heat Exchanger

Refer to Figure 25 for typical seawater plumbing arrangement.

  1. Connect seawater pump to Seakeeper dedicated through-hull fitting. A strainer and seacock valve should generally be installed between the seawater inlet and the pump.
  2. Connect seawater from installer supplied pump to lower 3/4 in. (19 mm) hose barb on heat exchanger. Use the same practices as other below waterline seawater plumbing.
  3. Connect seawater discharge to overboard drain. Use the same practices as other below waterline seawater plumbing.
  4. Required flow rate is 2 GPM (7.6 LPM) minimum and 6 GPM (22.7 LPM) maximum.
  5. In addition to initial operation at dock, new Seakeeper installations should be checked for minimum 2 GPM (7.6 LPM) flow while vessel is at speed and when backing down.
    1. If no other method of confirming flow is available, discharge line may be temporarily diverted to a bucket. Flow is calculated from time to fill a known volume.
    2. Flowrates in excess of 6 GPM (22.7 LPM) could affect heat exchanger life.
  6. Inspect raw water plumbing after sea trial for any signs of leakage.
Figure 25 – Typical Seawater Plumbing Arrangement

4.4 Seakeeper Optional DC Seawater Pump

  1. Seakeeper offers a self-priming DC Seawater pump as an optional addition, P/N 30331 – DC Seawater Pump Assembly, shown in Figure 26.
  2. The Seakeeper Seawater Pump is a 24 VDC pump operated at 12 VDC for the Seakeeper 2 and maintains a seawater flow of approximately 2.5 GPM (9.5 LPM) at 12 VDC.
  3. The pump assembly is pre-wired for connection to Seakeeper 2 Cable 5 and includes a seawater strainer and various fittings. The pump specifications are as follows:

NOTE: Use only SeaFlo-provided threaded fittings for DC Seawater Pump 30331.

Volts24 VDC (intended for 12 VDC operation with Seakeeper 2)
Flowrate2.5 GPM (9.5 LPM), at 12 VDC
Overcurrent Protection Rating15 A
Ignition Protection RatingISO 8846 or equivalent
Figure 26 Seakeeper DC Seawater Pump Assembly (P/N 30331)

4.5 Adding Coolant

  1. The Seakeeper 2 cooling system is filled to proper level when shipped. If level has dropped, check for evidence of leaks at all connections before adding fluid as described below. If coolant is at the correct level, skip to Step 5.
  2. The minimum and maximum glycol fill levels are shown in Figure 27.
Figure 27 Seakeeper Coolant Level
  1. Mix 50% ethylene glycol with 50% distilled water in a clean container. Refer to Table 1 or glycol manufacturer’s literature for freezing points.
    1. It is required that ethylene glycol with corrosion inhibitors be used. Most commercially available glycol has these additives standard.
  1. Remove reservoir cap and pour mixture in until level reaches top face of the reservoir enclosure, as shown in Figure 27.
    1. Filling reservoir above this level will not cause any damage but coolant may be expelled from the vented cap due to normal thermal expansion of coolant.
  2. Once the Seakeeper 2 and DC seawater pump are connected to 12 VDC power:
    1. Check the Seakeeper Display interface for any ALARMS.
    2. Cycle the Seakeeper 2 power, and press the POWER ON button.
    3. The flywheel will start to spin, and the glycol pump will start.
    4. Recheck glycol level with fluid circulating in coolant circuit to ensure the correct fill level is maintained.
  3. After several minutes of running, press POWER OFF button.
  4. The cooling system is self-purging. If small amounts of air are in the system, they should be dislodged during the first sea trial. Recheck level after sea trial and add fluid if required.

    NOTE: It is not uncommon to see some air in the coolant system. It is normal and will not affect operation.

5.0 Installation Requirements

6.0 Installation and Start Up Checklist

6.1 Installation and Start Up Introduction

Reference Documents:

The Installation and Start Up Checklists in this section provide an overview of the primary steps covered in the installation manual and should be referenced throughout the installation process. Upon completion of the
Seakeeper 2 installation, the installer should commission each Seakeeper unit with the Seakeeper Commissioning Form (90437). The Commissioning Checklist Work Instruction (SWI-105) provides a checklist of items to inspect and verify during the commissioning process and serves as a supplement to the Seakeeper Commissioning Form (90437).

All Seakeeper stabilizers should be commissioned to verify installation specifications and requirements have been implemented properly. The commissioning process should include completion of the Seakeeper
Commissioning Form (90437), all the items in the Installation Checklist, and verification of Seakeeper 2 operation without alarms or abnormal behavior.

6.2 Installation Checklist

Mechanical Checklist
(Reference Section: 2.0 Mechanical Installation)

  • Seakeeper foundation installed per requirements of the Seakeeper 2 Bolt-In Installation Details.
  • Clearances around Seakeeper meet service and operating specifications and no obstructions are within the Seakeeper envelope
  • Seakeeper supplied foundation bolts torqued to specification

Electrical Checklist
(Reference Seakeeper Drawing No. 90470 – Seakeeper 2 Cable Block Diagram & Section: 3.0 Electrical Installation)

Mount Components

  • Display (near helm)

Connect Seakeeper and Customer Supplied Cables

  • High Current 12 VDC Conductors (Seakeeper Supplied)
    • Connect High Current DC Input cables (P/N: 20335 and 20336) to customer supplied 2 AWG B+ and B- conductors to allow for routing to 12 VDC power source.
    • Connect High Current DC Input B+ conductor (red) through 100 A circuit breaker(customer-supplied) and a dedicated battery isolation switch (customer-supplied), directly to the battery positive terminal or bus bar.
    • Connect High Current Input B- conductor (black) to battery negative terminal or DC negative bus bar.

      NOTE: If the 2 AWG high-current 12V power input conductors are shortened or lengthened, use heavy-duty eyelet (closed end) terminals such as Molex19221-0235.
  • Ground Cable (Customer Supplied)
    • Install lugs on both ends of customer-supplied 4 AWG ground cable.
    • Connect one end of Ground Cable to nearest vessel ground and other end to Seakeeper foundation.
    • Vessel grounding bus to comply with:
      * EM/IEC 60204-1 Clauses 6.3.3 and 8.2.3
      * ABYC E-11 July 2018 Clauses 11.5.2 and 11.16.1.
  • Low Current 12 VDC Power Input Cable (Seakeeper Supplied)
    • Connect DC Input positive (red) cable (P/N: 20248) directly to a customer-supplied 15 A circuit breaker, then to the dedicated battery isolation switch
    • Connect DC Input negative (black) cable (P/N: 20248) to the DC negative bus bar or battery negative terminal.
    • Plug DC Input Cable connector end into the DT-Series connector labelled Low-Current 12 VDC in connector on the Seakeeper wire harness.
  • DC Seawater Pump Input Cable (Seakeeper Supplied)
    • Connect Seawater Pump Input positive (red) cable (P/N: 30327) directly to a customer-supplied circuit breaker corresponding to the seawater pump overcurrent protection rating (max 15 A), then to the dedicated battery isolation switch.
    • Connect Seawater Pump Input negative (black) cable (P/N: 30327) to the DC main negative bus bar or battery negative terminal.
  • DC Seawater Pump Output Cable (Seakeeper Supplied)
    • Connect female end of DC Seawater Pump Output Cable (P/N 20334) to customer supplied 12 VDC, 15 A seawater pump.
    • Plug male end connector of DC Seawater Pump Output Cable (P/N 20334) into mating connector on the Seakeeper wire harness

Cooling Checklist
(Reference Installation Manual Section: Cooling Installation)

  • Connect seawater hoses / open sea cocks to heat exchanger and test seawater pump.
  • Verify 2 GPM (7.6 LPM) minimum and 6 GPM (22.7 LPM) maximum seawater flow through heat exchanger under all operating conditions of the boat. (The seawater pump output will operate for two minutes after the Seakeeper is turned on. During operation, the seawater pump output is turned on and off based on the temperature of the Seakeeper)
  • Verify coolant level in heat exchanger coolant reservoir.

Start Up Checklist
(Reference Installation Manual Section: Start Up & Operation Manual Section: System Operation)

  • Remove lifting bolts and install cover panels
  • Turn on 12 VDC 15 A circuit breaker
  • Turn on 12 VDC 100 A circuit breaker
  • Verify display works and no ALARMS are present
    • If display does not work, turn off both circuit breakers immediately
    • Check polarity of 12 VDC 15 A power per Section 2.2.5
  • Follow instructions in Installation Manual Section: Start Up Instructions, to turn on the Seakeeper
  • Verify seawater pump turns on when the Seakeeper is turned ON
  • Verify that no ALARMS are present
  • Follow instructions in Installation Manual Section: Start Up Instructions, to turn off the Seakeeper
  • DC power and seawater pump may be turned off after the Seakeeper is turned off by placing the Seakeeper in LOCK mode and turning the Seakeeper off
  • Seakeeper 2 takes 16+ hours to coast down to 0 RPM from full speed

6.3 Start Up Checklist

Refer to Seakeeper 2 Operation Manual, Start Up Section for detailed start up instructions.

Prior to beginning the start-up sequence all previous Sections of the Installation Manual for Mechanical, Electrical, and Cooling installation must be complete. Before continuing, the Seakeeper 3 cover must be installed, and the operating clearances must be clear of personnel and equipment

CHECKREQUIREMENT TO BE MET
Remove lifting eyebolts and install sealing bolts (M10-1.25 X 12 mm) and flat washers into lifting eyeholes and install cover.
Energize battery isolation switch, high-current 100 A breaker, low-current 15 A breaker, and seawater pump breaker.
Verify Seakeeper display is active and no alarms present.

* If the Seakeeper 3 display does not activate, turn off all circuit breakers immediately and check all wiring connections.
Check that battery voltage exceeds 12 VDC. A minimum battery voltage of 11 VDC is required for the duration of Seakeeper spool-up.
Override seawater pump “ON” and verify flow at seawater outlet.
(To activate override, at 0 RPM flywheel speed, hold down SERVICE button wrench icon for 5 seconds to reveal override screen)
Deactivate seawater pump when completed obtaining seawater flow rate.
Press Seakeeper ON/OFF Button and follow instructions in Seakeeper 2 Operation Manual for complete start-up instructions.
Verify no alarms are present.
Power Seakeeper 2 down, the Seakeeper 2 flywheel will take 2+ hours to coast down to 0 RPM.

5.1 Installation Requirements Introduction

The Installation Requirements section outlines the components and tools needed for the Seakeeper 2 Installation that are not included within the scope of supply. Seakeeper offers Core Installation Kits which provide the required components for DC Seakeeper installations. These kits are outline in the DC Installation Kits Technical Bulletin (TB-90575).

7.0 Revision History

RevisionDescriptionDate
2Mounting screw torque change01JUN2018
3Seawater cooling modifications07AUG202
4ConnectBox release changes added. New bolt-in installation kit and details added. Added crate stacking recommendations.21JUL2023

5.2 Supplies Required for Installation

(Not Supplied With the Seakeeper)

ItemDescriptionQtyInstallation Manual Reference SectionOther ReferenceSystem
1Soundproofing ConsiderationsSelection of Installation LocationMechanical
2Spreader bar for lifting the Seakeeper1Transport and UnpackingMechanical
3Seakeeper 2 Fixture Kit1Bolt-In InstallationP/N 90473Mechanical
4Hose clamps for seawater plumbing to ¾ in. (19 mm) hose barb (2 per hose barb)4Connecting Seawater to Heat ExchangerDwg 90490Cooling
53/4 in. (19 mm) ID HoseARConnecting Seawater to Heat ExchangerDwg 90490Cooling
6Seacock Valve1Connecting Seawater to Heat ExchangerDwg 90490Cooling
7Seawater Strainer (included with Seakeeper Seawater Pump (P/N 30331))1Connecting Seawater to Heat ExchangerDwg 90490Cooling
8Through-Hull Fittings (1 high speed pick up and 1 overboard discharge)2Connecting Seawater to Heat ExchangerDwg 90490Cooling
9M6 terminal lug for grounding Seakeeper at rear brace1Electrical Equipment Ground Connections Dwg 90470 Electrical
10Cable, 4 AWG, for grounding Seakeeper at foundation to vessel ground (used with item 5)ARElectrical Equipment Ground Connections Dwg 90470Electrical
11Seawater pump, 12 VDC, 15A max1Electrical Equipment DC Pump Power Dwg 90470 Electrical
12100 A Circuit breaker for Conductor 11Electrical Equipment High Current Power Input Dwg 90470 Electrical
1315 A Circuit breaker for Low Current Power and DC Seawater Pump2Electrical Equipment Low Current Power Input Dwg 90470 Electrical
14Battery Isolator Switch1Electrical Equipment Power ConnectionsDwg 90470Electrical
15Marine SealantARBolt-In InstallationDWG 90487Mechanical
16Nickel-based Anti-SeizeARBolt-In InstallationDWG 90487Mechanical

AR = As Required
Dwg = Drawing

5.3 Tools Required for Installation

List of Common Tools That May Be Required for Installation

ItemDescriptionUse
1Hoist, Forklift, or CraneUnpacking and lifting Seakeeper 3 into position
2Transfer Punch KitLocate foundation hole penetrations
3Drill / Drill PressBolt hole penetrations
4Threaded Insert Installation KitTap and install threaded inserts (M14-2 X 1.5)
5Flexible Extendable Magnet, McMaster P/N: 3838A42 or similarLowering foundation bolts into place
61/2″ Drive Torque WrenchFoundation Bolts (155 ft-lbs/210 Nm)
712 – 18″ Extension, 1/2″ DriveFoundation Bolts
824mm Socket, 1/2″ DriveFoundation Bolts
9Utility KnifeScoring Cable Jackets
10Wire cutterDC Power cables
11Wire stripperDC Power cables
12Greenlee K05-Synchro Crimp Tool or equivalent12 VDC High-Current Input Cables, 2AWG Ground Cable, 4 AWG
13Heat GunFor cables 1, 2, and 6 heat shrink
14¼ in. (7mm) Nut Driver / Flat Head ScrewdriverHose clamps
15Fish TapeCable Pulls
16Hole SawThru-hull fittings